"We wish to compliment you on the excellent report rendered for the subject plant. The existing and additional new facilities were clearly presented. The breadth of data developed was extensive. And finally, the over-all organization and presentation of data was both practical and attractive. Many thanks."

Leo Fyer, Sr. E.E.
Alvarado Water Filtration Plan
t


Seattle Office
16122 SE 266th Street
Covington, WA 98042
(253) 639-8535 P.
(253) 639-8685 F.
Fuhr@PowerStudies.com

San Francisco Office
2400 Third Street
San Francisco, CA 94107
(415) 828-0529
Tran@PowerStudies.com

Puget Sound Energy
Feeder to Crystal Mountain Ski Resort Harmonic Investigation
Puget Sound Energy is a utility company serving Western Washington. They noticed that the voltage had an excessive amount of harmonics and the %THD exceeded the IEEE-519 guidelines.

Puget Sound Energy hired PowerStudies.com, to model their distribution system from the Greenwater Substation to the Crystal Mountain Ski Resort. The purpose of this study was to determine why the voltage distortion was so high at the location.

The engineers at PowerStudies.com found that due to the underground cable capacitance and system transformers, the system was tuned to the 5th harmonic. The ski resort has numerous variable speed drives that produce 5th harmonic currents. These currents along with the system tuned to the 5th harmonic caused the high %THD.

PowerStudies.com worked with the utility to redesign the distribution system and to shift the system resonant point to an even number.